Honeywell XNX XNX-AMAV-FHNNN – no sensor (transmitter body), mV, ATEX, Aluminium, M25

XNX-AMAV-FHNNN is a Honeywell XNX universal transmitter body with the mV personality, ATEX / IECEx (INMETRO on selected MPD SKUs), 4 × M25 entries, LM25 aluminium (painted), Foundation Fieldbus + 4–20 mA HART, local HART port on the transmitter, and no MPD sensor in the carton. Order it when the field later fits an MPD catalytic or MPD IR head (CB1 / IV1 / IF1 / IC1) instead of a factory-configured detector.

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-FHNNN, 316SS XNX-AMSV-FHNNN, other approval XNX-UTAV-FHNNN. XNX-AMAV-FHNNN · XNX-AMSV-FHNNN · XNX-UTAV-FHNNN

XNX-AMAV-FHNNN Honeywell XNX sensor not fitted Aluminium M25

Part-number decode

SegmentMeaningThis SKU
XNXHoneywell XNX universal transmitterXNX
A / UApproval A=ATEX/IECEx; U=UL/cULA
M / TEntry M=M25; T=3/4" NPTM
A / SEnclosure A=aluminium; S=316SSA
V / I / EPersonality V=mV(MPD); I=IR Optima/Excel; E=ECV
N / R / M / FOption N=HART only; R=relays; M=Modbus; F=FFBF
N / HLocal HART port N=no; H=yesH
NNNno sensor (transmitter body)NNN

Same sensor, swap enclosure/approval: aluminium XNX-AMAV-FHNNN, 316SS XNX-AMSV-FHNNN, other approval XNX-UTAV-FHNNN.

Technical specifications

Category变送器本体
PersonalitymV personality (MPD catalytic / MPD IR)
Sensor / rangeno sensor (transmitter body)
Targetbody / sensor not fitted
Principlepersonality board only
OutputFoundation Fieldbus + 4–20 mA HART
Local HARTlocal HART port on the transmitter
Supply16–32 VDC (24 VDC nominal)
EnclosureLM25 aluminium (painted)
Entries4 × M25
DisplayBacklit LCD, magnetic-wand menus
IngressIP66
ApprovalsATEX / IECEx (INMETRO on selected MPD SKUs)
Temperature−40~+65 ℃
Massapprox. 2.8 kg
Mates withHoneywell MPD catalytic bead or MPD infrared sensors

Why this personality / sensor

The mV personality is the millivolt interface for Honeywell MPD heads. Catalytic and MPD IR share that board; an IR Optima/Excel head will not talk to this SKU, and an electrochemical cell needs the EC personality. Buy a body when the sensor slate is still open or when you stock transmitters separately from MPD cartridges.

Personality and replaceable parts

XNX-AMAV-FHNNN uses the mV personality (MPD catalytic / MPD IR) board and mates with Honeywell MPD catalytic bead or MPD infrared sensors. This SKU ships without a sensor; order the head by gas. Spares live on product-3991. Do not substitute Sensepoint XCD cartridges on XNX.

Typical applications

Typical body SKUs sit in a warehouse next to mixed MPD stock: pump rooms that may take catalytic LEL, biogas roofs that need methane IR, LPG pits that need propane IR, and inerting cabinets that need CO₂. The transmitter is already certified and threaded; you only mate the MPD later.

Selection contrast

P/NGasRangeOptionBody
XNX-AMSV-FHNNNbodyFFB316SS
XNX-UTAV-FHNNNbodyFFBAluminium
XNX-AMAV-FHCB1LEL0–100 %LELFFBAluminium
XNX-AMAV-FHIV1CH₄0–100 %LELFFBAluminium
XNX-AMAV-FHIF1C₃H₈0–100 %LELFFBAluminium
XNX-AMAV-FHIC1CO₂0–5 %v/vFFBAluminium
XNX-AMAV-NHNNNbodyHARTAluminium

XNX family matrix

Installation and wiring

Wall-mount XNX-AMAV-FHNNN (LM25 aluminium (painted), approx. 2.8 kg) on a rigid stand sized for that mass. This SKU uses 4 × M25 entries—glands must match; do not retap XNX-AMAV-FHNNN. Land XNX-AMAV-FHNNN 4–20 mA HART per the loop drawing; relays/Modbus/FFB exist only on the matching option board. Magnetic-wand menus on the XNX-AMAV-FHNNN lid stay non-intrusive. XNX-AMAV-FHNNN is a body: wall-mount the transmitter first and mate the head after the personality is confirmed—do not buy a configured SKU until the gas is frozen.

FAQ

Can I add an MPD sensor to XNX-AMAV-FHNNN later?
XNX-AMAV-FHNNN ships as a transmitter body. mV personalities accept MPD CB1/IV1/IF1/IC1 heads; IR personalities need Optima/Excel; EC personalities need XNX electrochemical cells. Do not mix those three families on this board.
Is XNX-AMAV-FHNNN a complete gas detector?
No. XNX-AMAV-FHNNN is electronics and enclosure only. A configured detector has a three-character sensor code such as CB1 instead of NNN.
When should I swap XNX-AMAV-FHNNN aluminium for 316SS?
Use XNX-AMAV-FHNNN (aluminium, ~2.8 kg) in inland, painted plant. Coastal, splash and sour-water decks should move to stainless sibling XNX-AMSV-FHNNN.
Can I convert XNX-AMAV-FHNNN from ATEX M25 to NPT in the field?
No. XNX-AMAV-FHNNN flameproof entries are machined M25. North-American NPT is UL sibling XNX-UTAV-FHNNN, not an adaptor on this ATEX body.
Is XNX-AMAV-FHNNN the same as Modbus?
No. XNX-AMAV-FHNNN is Foundation Fieldbus. Modbus RTU is sibling XNX-AMAV-MHNNN. Both still carry 4–20 mA HART on XNX.

Documents

Honeywell XNX datasheet / manual · On-site XNX selection matrix

Availability and enquiry

Stock is lot-based. If this box is out, jump to 316SS XNX-AMSV-FHNNN or UL XNX-UTAV-FHNNN rather than a dead SKU.