MIDAS S2-I-SF6 | Honeywell Midas® sulfur hexafluoride ppm SF₆
MIDAS S2-I-SF6 is a Honeywell Midas® IR cartridge for sulfur hexafluoride (SF₆), range ppm SF₆, IR. It plugs into the MIDAS-T-004 extractive transmitter — not a Sensepoint XCD diffusion head. Sample line up to 30 m FEP at ~500 mL/min.

Mechanical & wiring figures




فك رقم القطعة
| الجزء | المعنى | هذا الرمز |
|---|---|---|
| MIDAS | Honeywell Midas® extractive | MIDAS |
| SF6 | sulfur hexafluoride | SF6 |
| S2 | Midas S2 IR generation | S2 |
المواصفات
| Category | خرطوش IR |
|---|---|
| Gas | SF₆ / sulfur hexafluoride |
| Range | ppm SF₆ |
| Principle | IR |
| Flow | approx. 500 mL/min |
| Sample length | 2–30 m FEP |
| Supply | 24 VDC or PoE 48 V |
| Outputs | 0–21 mA + 3 relays + Modbus TCP/PoE |
| Temperature | 0–40 °C (0–30 °C with pyrolyzer) |
| Size / mass | 150×65×153 mm / 0.8 kg |
| Approvals | CE, EN 50270, UL 61010-1, IEEE 802.3af |
Transmitter 150×65×153 mm / 0.8 kg; NF₃ pyrolyzer 70×63×85 mm / 0.41 kg; high-temp PFC pyrolyzer 100×101×140 mm / 1.36 kg.
لماذا هذا الرمز
Midas is extractive: the cell sits in the tool cabinet while FEP pulls sample from the valve box. sulfur hexafluoride uses IR. Pyrolyzed species need MIDAS-T-00P / T-HTP / T-NP1 or the cartridge will not read.
الملحقات وقطع الغيار
MIDAS S2-I-SF6 mates to MIDAS-T-004. Pump MIDAS-A-007, internal filter MIDAS-A-009. Do not substitute an electrochemical cartridge for this IR cell. Calibration notes live on product-2679.
تطبيقات نموذجية
Gas cabinets, VMBs, wet benches and CVD/etch exhaust. MIDAS S2-I-SF6 locks gas and cartridge life; budget transmitter, pump A-007 and internal filter A-009 on the PM cycle.
مقارنة
| P/N | Type | Gas | Range |
|---|---|---|---|
| MIDAS-T-004 | مرسل استخلاصي | MIDAS-T-004 | — |
| MIDAS-I-CO2 | خرطوش IR | CO₂ | 0–2.0 %vol |
| MIDAS-I-SF6 | خرطوش IR | SF₆ | ppm SF₆ |
| MIDAS S2-I-CH2 | خرطوش IR | CH₂F₂ | ppm CH₂F₂ |
| MIDAS S2-I-CH3 | خرطوش IR | CH₃F | ppm CH₃F |
| MIDAS S2-I-CO2 | خرطوش IR | CO₂ | 0–2.0 %vol |
| MIDAS-I-COS | خرطوش IR | COS | ppm COS |
التركيب وخط العينة
Wall-mount MIDAS-T-004 on the pre-drilled chassis or DIN kit A-036, then insert MIDAS S2-I-SF6. Sample 1/8″ID×1/4″OD FEP to 30 m; exhaust 1/4″ID×3/8″OD to 30 m. End-of-line filter 0780248 or 1830-0055/0027 by gas. 24 VDC (−15%/+10%) or PoE 48 V; pyrolyzer load up to 12.95 W. 0–40 °C, 0–30 °C with pyrolyzer.
أسئلة شائعة
- Can MIDAS S2-I-SF6 plug into Sensepoint XCD?
- No. Midas is an extractive cartridge; XCD is a diffusion sensor housing. They do not mate.
- Does MIDAS S2-I-SF6 need a pyrolyzer?
- Gases marked ** (CH₂F₂, C₄F₆, C₅F₈, NF₃, CH₃F) need MIDAS-T-00P / T-HTP / T-NP1 plus a ventilated cover.
- How is 4–20 mA landed on MIDAS S2-I-SF6?
- 3-wire sink, 3-wire source or 4-wire isolated 0–21 mA; plus 3 relays and Modbus TCP / PoE. Max 14 AWG.
وثائق
Datasheet PDF · Chinese manual · English technical manual · مصفوفة عائلة Midas
التسعير
المخزون حسب الدفعة. إذا نفد خرطوش E فانظر خرطوش S لنفس الغاز. غازات التفكك الحراري تتطلب طلب المفكك مع المرسل.